8. Troubleshooting
252
SMGB0079 rev.0 - 01/2013
8.2.4 Alarm codes for the KPI (E/H/X)3E Series and DX Interface
Code
No.
DX-
KIT2
KPI-
S3
KPI-
Active
Category
Type of Abnormality
Main cause
01
o
-
o
Indoor
Activation of protection device
Float switch activation (high water level in drain hose or
abnormality in drain pipe, float switch or drain pan).
03
o
-
o
Transmission Transmission Error
Outdoor fuse meltdown, Indoor/outdoor connection wir-
ing (breaking, wiring error, etc.)
11
o
o
o
Indoor
Air inlet thermistor (RA for KPI)
Loose, disconnected, broken or short-circuited connector
12
o
o
o
Indoor
Air outlet thermistor (OA for KPI)
Loose, disconnected, broken or short-circuited connector
13
o
-
o
Indoor
Liquid pipe thermistor
Loose, disconnected, broken or short-circuited connector
14
o
-
o
Indoor
Gas pipe thermistor
Loose, disconnected, broken or short-circuited connector
15
-
-
-
Indoor
Fresh Outdoor Air Thermistor
(Econofresh)
Loose, disconnected, broken or short-circuited connector
16
-
-
o
Indoor
Air inlet DX Coil thermistor (Tincoil)
Loose, disconnected, broken or short-circuited connector
17
-
-
o
Indoor
Air outlet DX Coil thermistor (Tout-
coil)
Loose, disconnected, broken or short-circuited connector
18
(o)
o
o
Indoor
Indoor RA fan protection device
activation for KP
Fan motor overheating, locking.
19
o
o
o
Indoor
Indoor OA fan protection device
activation for KPI or DX-KIT2 Fan
Fan motor overheating, locking.,
31
o
-
o
System
Incorrect setting of outdoor and
indoor units
Outdoor/Indoor Unit capacity setting error, Indoor total ca-
pacity excessively large/small
35
o
-
o
System
Indoor Unit Number Setting Error
Indoor units with the same number exist in a refrigerant
piping system
70
o
o
o
Indoor
Abnormal transmission between
PCB1 and PCB2
Loose, disconnected
71
o
o
o
Indoor
Incorrect PCBs setting
Wrong setting are performed in PCBs
EE
o
-
o
Compressor
Compressor protection alarm (can-
not be reset from the remote con-
troller)
This alarm code is displayed when the following alarms
are triggered three times within six hours: 02,07,08,39,43
to 45, 47
74
-
-
-
Indoor
Remote sensor thermistor (Trem) Loose, disconnected, broken or short-circuited con-
nector
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......