12. Maintenance notes
464
SMGB0079 rev.0 - 01/2013
12.6 Pump-down method for replacing the compressor
No.
Procedure
Remarks
1
Turn off the main switch of the outdoor unit.
2
Remove the covers the thermistor the crankcase heater the power
wirings and other items according to the chapter 10.
Make sure that the terminal part of the detached power supply
wires is not exposed by the winding insulation tape and other items.
3
Attach the manifold to the check joint of the high pressure side and
the low-pressure side of the outdoor unit.
—
4
Turn on the main switch of the outdoor unit.
—
5
Set the exclusion of the compressor by setting the DSW so that a
broken compressor will not work. You can set the exclusion of the
compressor by setting the DSW1-4 in ON position.
—
6
The compressor replacing mode is performed:
•
The DSW1-4 on the outdoor unit PCB→ON (The cooling is
run).
•
This operation is performed for up to a maximum of ten minutes.
•
If the inverter compressor is excluded the operation starts after
three minutes.
7
The operation finishes when one of the following conditions occurs:
1
Ten minutes have passed and STP is displayed in seven seg-
ments.
2
“08” is displayed in seven segments.
3
When Ps< 0.1 MPa is continued for one minute in ten minutes
STP is displayed in seven seconds and the operation finishes.
•
The operation may finished when any of the conditions 1) to
3) occurs.
8
Close the liquid stop valve completely.
To avoid the spillage of all the refrigerant if the check valve is
broken.
9
Check for a leakage of the check valve on the discharge gas side:
•
DSW4-4 (enforced stoppage of the compressor) → ON so that
the compressor will not run although the running command is
sent from the remote control switch.
•
Check that variation of Ps on the outdoor unit PCB is 17 se-
conds. Make sure that the Ps increase is within 0.03 Mpa in two
minutes after the Ps increase at the stoppage (during approxi-
mately five minutes). Also make sure that Pd > Ps.
•
When you stop the compressor for replacing:
•
You can check the leakage of the check valve by means of the
Ps variation because the SVA opens so that the discharge gas
side of the inverter compressor can connect to the low-pressure
side.
•
0.03 MPa/2 minutes is within the permissible limits for the check
valve on the discharge gas side.
•
The leakage of the check valve may cause an incorrect brazing
due to the gas pressure at the brazing of the discharge piping.
•
If the compressor-replacing mode is performed again set the
DSW4-4 to OFF and keep the DSW4-4 at the OFF side during
ten minutes. Then start according to the procedure No. 6.
10
Collect the refrigerant by means of the refrigerant collection:
•
Perform either A or B depending on the process 10.
-
The leak rate at the process 10 is within the specification
→Collect the refrigerant only at the low-pressure side.
-
The leak rate at the process 10 is greater than the
specification → Collect all the refrigerant of the outdoor
unit side by means of the machine.
•
The discharge of the refrigerant in the atmosphere is strictly
forbidden. Make sure that the refrigerant is collected by the co-
llector.
•
Keep a note of the quantity of the collected refrigerant.
11
After collecting the refrigerant remove the change hose (collector
side) of the low-pressure side so that the low-pressure side of the
refrigerant cycle will be the atmosphere pressure.
•
Make sure that there is no pressure increase of the low-pressu-
re sides after collecting the refrigerant.
•
Make sure that the refrigerant cycle is the atmosphere pressure.
Otherwise problems such as the blowing of gas and the suction
of the cutting material) may occur when you are removing the
compressors.
12
Turn OFF the main switch of the outdoor unit.
—
13
Perform the replacement of the compressor and the change of the
refrigerant oil according to the section “replacing the compressor”.
Make sure that you follow the instructions.
14
Perform the vacuum from the check joint of the low-pressure side.
If you collect the refrigerant only on the low-pressure side (A in 11).
You cannot perform the vacuum of the refrigerant from the check
joint of the high-pressure side.
15
Open the liquid stop valve and the gas stop valve completely when
you finish the vacuum.
—
16
Make sure that the power is turned OFF and attach the following
items: the power supply wire the thermistor the crankcase heater
the 63H wiring the panel and the nut).
—
17
Set the DSW back to the original setting. Make sure that all the
wirings to the compressor are connected correctly.
—
18
Recharge the refrigerant that is collected in the process by the stop
valve of the liquid side during the cooling at the TEST RUN mode.
If the replacement of the compressor takes more than two hours an
additional change of the refrigerant is necessary. Additional change
= (replacing time – 2 hours) x 0.5 kg.
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......