7. Test run
181
SMGB0079 rev.0 - 01/2013
7
Additional information for “Check list on compressor”
Check item
Additional information (mechanism of compressor failure)
1 & 2
The liquid refrigerant return volume to the compressor is controlled by the discharge gas temperature Td when
compressor is operating. If Td thermistor is disconnected, the liquid refrigerant return volume will become small
by detecting the temperature even if the actual discharge gas temperature is high. Therefore, this abnormal
overheating by detecting the temperature operation will result in insulation failure of the motor winding.
3 & 4
Overcurrent control (operating frequency control) is performed by detecting current by the PCB2. In this case,
winding insulation failure will occur, since control is not available in spite of actually high current.
5 & 6
The current sensor checks phase and adjusts output electrical wave in addition to the above mentioned items. If
fault occurs, the output electrical wave becomes unstable giving stress to the motor winding, resulting in winding
insulation failure.
7 & 8
During a cooling operation, SH is controlled by MV of each indoor units. During a heating operation, Td is
controlled by MV1. If expansion valves are incorrectly connected, correct control is not available, resulting in
compressor seizure depending on liquid refrigerant returning conditions or motor winding insulation failure de-
pending on overheating conditions.
9
If the refrigeration cycle and electrical system are incorrectly connected, abnormally low suction pressure ope-
ration is maintained or abnormally high discharge pressure operation is maintained, resulting in giving stress to
the compressor, since their correct control is not available.
10
If the expansion valve and electrical system are incorrectly connected, abnormally low suction pressure opera-
tion is maintained or abnormally high discharge pressure operation is maintained, resulting in giving stress to
the compressor, since their correct control is not available.
11
The compressor may be locked due to the liquid return operation during the cooling operation .
12
In the case that the contacting resistance becomes big, voltage imbalance among each phase will cause abnor-
mal overcurrent.
13
In this case, overcurrent will occur, efficiency will decrease or the motor winding will be excessively heated.
14
In the case, it will result in motor burning or compressor failure
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......