8. Troubleshooting
239
SMGB0079 rev.0 - 01/2013
8
Alarm code
53
Activation of transistor module (RAS-3HVNPE / RAS-(4-6)H(V)NCE)
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
-
IPM or Dip IPM and PCB2 have detecting function of abnormality. This alarm is indicated when the transistor mod-
ule detect the abnormality 7 times in 30 minutes including 7. Retry operation is performed up to the occurrence of
6 times.
Conditions:
• The abnormal current such as short circuited, grounded or the overcurrent occurs at the transistor module.
• The temperature at transistor module increases abnormally.
• The control voltage decreases.
• The angle difference between the shaft in compressor and the shaft in the control program e60deg.
Yes
Yes
Turn OFF power,
disconnect U, V, W
from compressor
terminals and restart.
Does the protecting
function activate? *3)
No
Is heat exchanger of
clogged?
Remove clogging or
replace heat exchanger.
Check the compressor.
Check the compressor.
Replace it if faulty.
Check fan motor.
No
Check
the compressor.
Normal
Failure of Inverter PCB.
Replace it.
Check pressure and
refrigerant cycle.
Is high pressure
increased?
Check clogging for
heat exchanger.
Abnormal
(Itc=1, 12)*
(Itc=21)*
Restart operation.
Compressor
stops after
few minutes.
Compressor
stops
immediately.
Faulty Inverter PCB
Replace it.
* Refer to the item 1.2.8 (D)
“Cause Code of Inverter Stoppage” for details.
N O T E
•
*1) Perform the high voltage discharge work by referring to the item
Procedure of checking other main parts
,
before checking and replacing the inverter components.
•
*2) Regarding replacing or checking method for inverter components, refer to item
Procedure of checking
other main parts
.
•
*3) Turn ON the No.1 switch of the dip switch DSW1 on PCB2 (inverter) when restarting with disconnecting the
terminals of the compressor. After troubleshooting, turn OFF the No.1 switch of the dip switch DSW1 on PCB2.
•
When the alarm code “53” is indicated, the outdoor fan motor (DC motor) ensure that DC fan motor is checked
according to the item
Procedure of checking other main parts
.
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......