8. Troubleshooting
185
SMGB0079 rev.0 - 01/2013
8
8.1.2 Failure of the power supply to the indoor unit and the remote control switch
•
The LED and the LCD are not indicated.
•
Not operated
If the fuses are blown out or a breaker is activated, investigate the cause of the overcurrent and take the necessary action.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Power failure or power is not ON
Measure the voltage by means of
the voltmeter
Supply the power
Blown out fuse or activation of the
breaker at the power source
Short circuit supplied between the
wires
Check for any uncovered part of
the wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the wires to earth
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure resistance between
wires and insulation resistance
Replace the fan motor and fuse
Blown out fuse at the control cir-
cuit
Short circuit supplied between the
wires
Check for any uncovered part of
the wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the control circuit
to earth
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of the transformer at the indoor unit side
Measure the voltage at the sec-
ondary side
Replace the transformer
Disconnected cable of the remote control switch
Connect the cable
Replace the cable or repair the
cable
Insufficient contacting at the con-
nectors of the remote control
switch
Insufficient connection or incorrect
connection of the indoor unit PCB
Check the connectors
Correctly connect the connector
Insufficient connection or incorrect
connection of the indoor unit PCB
in the remote control switch
Failure of the remote control switch
Check the remote control switch
by means of the self-check mode
*1)
Replace the remote control switch
if it failed
Failure of PCB
Unconnected wires to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the self-
check mode *2)
Replace PCB if it failed
Incorrect wiring connection
Take action according to the procedure that is displayed in “TEST RUN”
N O T E
•
*1): Refer to section
Self-checking of the remote control switch
.
•
*2): Refer to section
Self-checking procedure of PCB by means of the Remote Control Switch
.
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......