12. Maintenance notes
456
SMGB0079 rev.0 - 01/2013
12.1 General notes
12.1.1 Checking the power source and the wiring connection
Check the following items in the case of abnormal operation:
No.
Check item
Procedure
1
Is the breaker of the fuse cut
out?
Check the secondary voltage of the breaker and the fuse by means of a tester.
2
Is the secondary power source
on the transformer correct?
Disconnect the secondary side of the transformer and check the voltage by means of a tester.
Indoor unit
transformer
Secondary
side
Primary side
220, 230 or
240 V
Circuit and voltage
12 V
12 V
3
Is the wiring loosened or inco-
rrectly connected?
Check the wiring connection on the PCB.
•
Thermistor connectors
•
Connector of the remote control cable
•
Connector of the transformer
Each connector in a high-voltage circuitCheck the connectors according to the
electrical wiring
diagram.
12.1.2 Burnt-out compressor due to an insufficient refrigerant charge
Question and answer for the field work
Example 1: Burnt-out compressor due to an insufficient refrigerant charge
Phenomenon
After commissioning the alarm code “08” sometimes occurred and the compressors were burnt out after operating for two
months.
Cause
The refrigerant piping work was performed during the summer season. The additional refrigerant was not sufficiently
charged from the discharge gas side.
This insufficient refrigerant charge resulted in the overheating of the discharge gas and the oil deterioration which was
finally due to the separated operation despite the alarm code “08”.
Countermeasure
1
The compressor was replaced with a new compressor.
2
The correct refrigerant amount was charged according to the refrigerant piping length and the connected indoor units.
Remarks
Additional refrigerant charge: Open the liquid stop valves slightly when you charge the additional refrigerant from the
check joint of the liquid stop valves (the discharge gas side) during the cooling process. If the liquid stop valve is fully open
it is difficult to charge the additional refrigerant. Do not charge the refrigerant from the gas stop valve.
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......