Page | 50
Battery Load Test
EURO 280 Systems may be programmed to perform an automatic battery load test at every
power supply at 7.00am each day. This will drop the power supply voltage below the battery
voltage, whilst monitoring the system diagnostics. The test will NOT take place if:
The End Station siren and strobe Output are live
The system is in Engineer Mode
Any battery faults exists
Any mains fault exists
The site option is not selected
If the test has already started, it will be aborted if any of these conditions apply, other than
entry into Engineer Mode. If the test is aborted, it will NOT be performed until the next day.
This is selected in SITE OPTIONS under “Do Battery Load Test”. The test may also be
performed as required, under engineer control.
4.1.55 Test Outputs
The engineer can test all the Programmable Outputs on the End Station and the output
module. This test can also be used to test the STU/ATE pins, select the output types you have
chosen for the pins and test them, the signal will be then sent out on both the programmable
outputs and the STU/ATE pins.
4.1.56 Test Communications
If the engineer is using SIA or Contact ID to signal events, this function can be used to send a
test signal to the alarm receiving centre (ARC).
4.1.57 Engineer Test Menu
Engineer Tests
Using the
and
keys, scroll to
‘ENGINEER TESTS?
’
Press the
key
Sound To Play
Press the
key to select which
sound you would like to hear. Press the
key.
Walk Test?
Press the
key and Select the Areas
to be tested. Press the
key. The
display will scroll through all the inputs
not yet tested. Walk so that each input
is triggered, and a chime will sound as
inputs disappear from the scrolling list.
Press the
key. Once the last
remaining input has been tested, ‘Walk
Test Complete’ will be displayed, press
the
key to move to the next menu.
NOTE: If a just a specific input needs to be walk
tested, press
instead of selecting areas. This will
then allow specific inputs to be entered with the
numerical keys, pressing
after each input. Then
press
to walk test them.
Soak Control?
To enter the Soak Control press the
key. Enter the number of the
inputs you wish to soak test and press
. The input number shows on the
scrolling list. Repeat for each input to