Page | 22
Action
Status
Outputs
Shunt Input closed
(shunted)
Inputs within the Shunt Group
are inactive
The ‘Follow Input’ output is live
Shunt Group Input
triggered
No response
Shunt Input opened
(unshunted)
-
The ‘Follow Input’ output clears.
The ‘Shunt Fault’ output is live for
10 seconds.
After 10 seconds
Inputs in the Shunt Group are
active
Indications off.
Shunt Input opened
with an active detector
(attempting to
unshunt)
-
The ‘Follow Input’ output clears.
The ‘Shunt Fault’ output pulses
until the shunt is reset or the
input fault clears.
Active input clears
-
The ‘Shunt Fault’ output is live for
10 seconds. (Will not function
correctly on an ATE pin).
After 10 seconds
Inputs in the Shunt Group are
active
Indications off.
Shunt Group Input
triggered
Normal input response
(Note: depends upon the status of
the Area in which the shunt is
located).
Change Inputs
Using the
and
keys, scroll to
‘
CHANGE INPUTS?
’. Press the
key
Input
Select the input number you wish
to program and press
the
key.
Input Type
Select the shunt input type (type 18)
Shunt Inputs
Press the
key to assign inputs.
Enter the inputs you would like in the
shunt list, after each one press the
key. Each input selected will
scroll on the display on the bottom
line. If the input you have selected
doesn’t appear, make sure that input
is programmed correctly (Intruder,
Tamper, 24Hr or Entry Route).
Once they have all been entered
press the
key, and press the
key again.