Manual
HM1016ER1
Parameters Setting
Harsen
®
Page 30/54
NOTE:
“Configurable” means user can input the data manually according to the
sensor curve. It can be done only through the PC software.
When configuring, please input the “resistance-value” from small to big
one by one.
P-sensor type:
Used to configure the type of LOP sensor.
Optional kinds of built-in LOP sensors in controller.
Code
Mode
Note
1
close for low oil pressure
2
open for low oil pressure
3
VDO 5 bar
4
VDO 10 bar
5
Datcon 7 bar
6
Murphy 7 bar
7
Pre-set 1
8
Pre-set 2
9
Pre-set 3
10
Pre-set 4
11
Configurable
CAUTION:
The LOP sensor is used to measure the oil pressure, its accuracy is very
important to the protection of the Genset, so please match the right type
of the sensor or configure the right curve of the senor. Otherwise it may
cause engine damage.
The parameters appendix of LOP sensor:
VDO 5 bar:
P
(Bar)
0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5
R
(Ω)
11
29
47
65
82
100
117
134
151
167
184
VDO 10 bar:
P
(Bar)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
R
(Ω)
10
31
52
71
90
106
124
140
155
170
184
Datcon 7 bar:
P
(Bar)
0.0
0.7
1.4
2.1
2.8
3.4
4.1
4.8
5.5
6.2
6.9
R
(Ω)
240
200
165
135
115
95
78
63
48
35
25
Murphy 7 bar:
P
(Bar)
0.0
0.7
1.4
2.1
2.8
3.4
4.1
4.8
5.5
6.2
6.9
R
(Ω)
240
205
171
143
123
103
88
74
60
47
33
Pre-set 1:
P
(Bar)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
R
(Ω)
15
31
49
66
85
101
117
132
149
164
178