Manual
HM1016ER1
Panel Operation
Harsen
®
Page 6/54
START Button / LED / Return
The push button is used for manually start the Genset. When controller
is running in MANUAL mode, press this button to start the generator.
When in parameters setting mode, this button is used to return.
STOP / RESET Button / “
→
→
→
→
” Move Setting
The Push button is used for manually stops the Genset. No matter
what mode the controller is running, press and hold this button for
2sec to stop the generator, the mode of the controller will be default to
“MAN” mode automatically from “AUTO” or “TEST” mode and the
generator will be shut down after cool down period, during the cool
down period if you press and hold this button for 2sec again, the
generator will be shut down immediately.
If failure occurs, press this button, the shutdown alarm lockout can be
cleared.
When in parameters setting mode, this button is used to move to next
parameters setting position.
C/O Button
There are 2 C/O buttons respectively beside the Mains and Gen icons.
They are used to close/open the switches of Mains and Gen when
controller is running in MANUAL mode.
Shutdown Alarm (FAILURE) LED
The LED will illuminate permanently when shutdown alarm occurs.
Pre-alarm (WARNING) LED
The LED will illuminate permanently when pre-alarm occurs.
GEN. Normal LED
Gen. normal LED will illuminate after both voltage and frequency of the
Gen. reach loading voltage and frequency.
GCB/MCB Closed LED
LED will illuminate when GCB/MCB is closed and power supplied by
Gen / Mains, LED will flash when GCB / MCB failure occurs.
MAINS Normal LED
Mains normal LED will illuminate after both voltage and frequency of
the Mains reach the preset value range.