Manual
HM1016ER1
Outline Dimension Drawings and Controller Wiring
Harsen
®
Page 3/54
2.2 Terminal Connections:
Pin no.
Function Description
Signal
Dim
1
GEN. V
L1-N
input
0-346Vac
1mm²
2
GEN. V
L2-N
input
0-346Vac
1mm²
3
GEN. V
L3-N
input
0-346Vac
1mm²
4
GEN. Neutral
1mm²
5
Not used
6
MAINS V
L1-N
input
0-346Vac
1mm²
7
MAINS V
L2-N
input
0-346Vac
1mm²
8
MAINS V
L3-N
input
0-346Vac
1mm²
9
MAINS Neutral
1mm²
10
I1 Gen current input (S1)
0-5A
2.5mm²
11
I2 Gen current input (S1)
0-5A
2.5mm²
12
I3 Gen current input (S1)
0-5A
2.5mm²
13
Common port for current inputs (S2) 0-5A
2.5mm²
14
LOP sensor
<1K
Ω
2.5mm²
15
HET sensor
<1K
Ω
2.5mm²
16
Common port for sensor
2.5mm²
17
Common port for relay outputs
2.5mm²
18
Fuel solenoid relay output
N.O. contact, 16A/30Vdc
2.5mm²
19
Start (Crank) relay output
N.O. contact, 16A/30Vdc
2.5mm²
20
Relay output 3 (GCB close/open)
N.O. contact, 3A/30Vdc, configurable (1)
1mm²
21
Relay output 4 (MCB close/open)
N.O. contact, 3A/30Vdc, configurable (2)
1mm²
22
Relay output 5
N.O. contact, 3A/30Vdc, configurable (3)
1mm²
23
Relay output 6
N.O. contact, 3A/30Vdc, configurable (4)
1mm²
24
charger excitation power output
if not used, do not connect to negative
1mm²
25
Configurable digital input signal 1
low level is active
1mm²
26
Configurable digital input signal 2
low level is active
1mm²
27
Configurable digital input signal 3
low level is active
1mm²
28
Configurable digital input signal 4
low level is active
1mm²
29
Configurable digital input signal 5
low level is active
1mm²
30
Magnetic pick-up signal (+)
1-70Vac
2 cores
shielded
31
Common for configurable inputs and
magnetic pick-up signal (-)
32
Battery supply (+B)
2.5mm²
33
Battery supply {-B}
12V/24V (8-35Vdc continuous)
2.5mm²
34
Ground
2.5mm²
NOTE:
Relay output 3 and 4 are respectively configured as GCB and MCB
close/open relay when default setting, however both can be reconfigured
by user if required.