Manual
HM1016ER1
Parameters Setting
Harsen
®
Page 25/54
7.2 GENERATOR:
NO.
Items
Preset
Value Range
2.1
GEN-V under preALM
90%
20 to 200% / 0 not used
2.2
GEN-V under Alarm
0
20 to 200% / 0 not used
2.3
GEN-V over preALM
115%
20 to 200% / 999 not used
2.4
GEN-V over Alarm
999
20 to 200% / 999 not used
2.5
KW Overload preALM
999
20 to 200% / 999 not used
2.6
KW Overload Alarm
100%
20 to 200% / 999 not used
2.7
Alarm delay
5s
0 to 600s
2.8
Overcurrent level
100%
20 to 200% / 999 not used
2.9
Overcurrent delay
1s
1 to 20s
2.10
Overcurrent action
0
0 pre-alarm / 1 electrical trip / 2 shutdown
2.11
Loading Voltage
95%
20 to 200%
2.12
Loading Frequency
48.0Hz
10.0 to 100.0Hz
2.13
GEN. ON delay
5s
1 to 9999s
2.14
GCB closing time
5s
2 to 200s
2.15
Test mode
1
0 without load / 1 with load
Menu descriptions:
GEN-V under preALM:
Used to configure Gen under voltage pre-alarm value, the GEN-V under preALM is inactive when
parameter is configured as “0”.
Expressed by percentage, = “Rated Ph-N voltage” x ?%.
GEN-V under Alarm:
Used to configure Gen under voltage alarm value, the GEN-V under Alarm is inactive when
parameter is configured as “0”.
Expressed by percentage, = “Rated Ph-N voltage” x ?%.
GEN-V over preALM:
Used to configure Gen over voltage pre-alarm value, the GEN-V over preALM is inactive when
parameter is configured as “999”.
Expressed by percentage, = “Rated Ph-N voltage” x ?%.
GEN-V over Alarm:
Used to configure Gen over voltage alarm value, the GEN-V over Alarm is inactive when parameter
is configured as “999”.
Expressed by percentage, = “Rated Ph-N voltage” x ?%.
KW Overload preALM:
Used to configure the over load pre-alarm value, the KW Overload preALM is inactive when
parameter configured as “999”.
Expressed by percentage, use “Rated active power” as factor.