KW Overload Alarm:
Used to configure the over load alarm value, the KW Overload Alarm is inactive when parameter
configured as “999”.
Expressed by percentage, use “Rated active power” as factor.
Alarm delay:
Use a timer for confirmation of the alarm or pre-alarm.
Overcurrent level:
Used to configure the over current value of the Gen or the load, the overcurrent alarm is inactive
when parameter configured as “999”.
Expressed by percentage, use “Rated current” as factor.
Overcurrent delay:
Use a timer for confirmation of overcurrent alarm.
Overcurrent action:
Used to configure the action which is implemented after overcurrent alarm confirmed.
3 types of parameters can be configured: 0 pre-alarm (warning)/ 1 electrical trip/ 2 shutdown.
When parameter is configured as “0”, the pre-alarm (warning) LED illuminates and buzzer sounds if
over current happens, and LCD displays over current icon.
When parameter is configured as “1”, the pre-alarm(warning) LED illuminates and buzzer sounds if
over current happens, Genset will not shutdown, LCD displays over current icon.
When parameter is configured as “2”, the Shutdown alarm LED illuminates and buzzer sounds if
over current happens, the Genset will be shut down, LCD displays over current icon.
Loading Voltage:
Used to configure the voltage trigger value of the GCB close.
Expressed by percentage, use “Rated ph-voltage” as factor.
Loading Frequency:
Used to configure the frequency trigger value of the GCB close.
GEN. ON delay:
Use a timer for confirmation of voltage and frequency trigger value for Gen supply.
GCB closing time:
Use a timer for confirmation of the Gen Aux. Switch’s contact has been closed.
When the GCB output is energised, if the controller does not receive the feed back signal from the
Gen Aux. Switch’s contact after the “GCB closing time” has expired, then means Gen fails to load.
Test mode:
Used to select a function of the controller in the test mode.
There are two test modes, one is “0 without load”, stand for test the Genset without load (the GCB
close output will not be energised), another is “1 with load”, stand for test the Genset with load (the
GCB close output will be energised).