Manual
HM1016ER1
Parameters Setting
Harsen
®
Page 31/54
Pre-set 2:
P
(Bar)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
R
(Ω)
30
41
65
88
110
115
145
150
172
185
190
Pre-set 3:
P
(Bar)
0
1.7
3.4
5.2
6.9
8.6
10.3
R
(Ω)
21
36
52
72
84
100
120
Pre-set 4:
P
(Bar)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
R
(Ω)
195
155
127
107
88
72
61
54
48
NOTE:
“Configurable” means user can input the data manually according to the
sensor curve. It can be done only through PC software.
When configuring, please input the “resistance- measured value” from
small to big one by one.
Start delay:
Used to configure the time delay from the remote start signal is active to crank output is energised.
Crank attempt:
Used to configure how many times the controller repeat to crank the engine; this value is equal to
the maximum crank times.
Crank time:
Used to configure the maximum time permit of engine cranking.
Crank time add:
Used to adjust the maximum time permit of the repeat cranking.
The second time of crank time is equal to the first crank time plus the extra time. For example:
“crank time” set at 5s, “Crank time add” set at 3s, then since the second crank, the maximum crank
time permit is 8s.
CAUTION:
The maximum crank time permit can not exceed the range of the
equipment safety.
Crank rest:
The time between last crank and next crank.
Engine only can be cranked again after the crank rest time has expired.
Crank cutout RPM:
The crank cutout speed.
Crank cutout volt:
The crank disconnect voltage
Expressed by percentage, use “Rated ph-voltage” as factor.
When parameter configured as “999”, Crank cutout volt is inactive.