Manual
HM1016ER1
LCD displays and Menu System
Harsen
®
Page 50/54
9. LCD displays and Menu System
9.1
LCD displays measuring parameters:
Use a back-light TN LCD to display data and information. Each page can display multi-row information
simultaneously, and the corresponding icon displays each status and data clearly. Display all status
data and information needs several pages. Press “
” to scroll for viewing next page, it can be
configured as auto scroll as well. When alarm occurs, the alarm status and the corresponding alarm
icon are displayed on the LCD immediately.
Circularly displays each measuring parameter when generator is running:
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
→
NOTE:
When HET sensor or LOP sensor is set as “not used”, LCD will not display
the related data.
9.2
Setting running parameters
Press and hold “
” button 2sec to enter into parameter settings menu, then use “+” or “-” to scroll
page in the same menu list, press “
√
” enter into submenu, press “
” can return to upper menu, go to
menu 1.11 “
” to key in password first, or select the required item, press “
√
” enter into modify
mode, press “+” or “-”, LCD displays 0 0 0 0 when prompted enter password, then use “+” or “-” to
modify the first digital value, press “
→
” move to modify next digital value, the first digital value will be
displayed as “ ” after moving to next digital value, press “
√
” to confirm after the password is set as
2213, then you can modify parameters. Otherwise it will prompt to key in password again. Press and
hold “
” for more than 2sec or press “
” to quit parameter settings mode after finishing configuration.