8.2.2 Power supply:
Power specification:
DC voltage range
8-35Vdc continuous
Max. operating current
@12V, 300mA; @24V, 150mA
Cranking dropouts
0V for 80ms, assuming dc supply was at least 10V before dropout and
recovers to 5V, controller can be normally operated dispenses with
additional aux. power.
NOTE:
A switch or fuse for over current protection between power supply and
controller must be mounted, the recommended capacity is 1A.
When powering, the controller will generate significant instantaneous
peak current, the maximum instantaneous peak current is relative to the
power impedance. You must consider the peak current when choosing a
switch or fuse for over current protection.
8.2.3 The installations of LOP sensor, HET sensor, and Auxiliary sensor:
The connection for 2 poles sensor:
The connection for single pole sensor:
The connection for single pole / 2 poles sensor: