5. Environmental
HZI855 meets the following environmental requirements:
5.1. IP Rating
• IP65 door mounted with gasket in accessory.
• IP30 door mounted without gasket.
• IP2X on the back of the controller.
5.2. Operating Conditions
5.2.1. Temperature
• From -30 to + 70°C
NOTE: With limitations on the LCD screen that may show temporary distortion below -10°C.
5.2.2. Hygrometry
• 95% humidity without condensation at 55°C.
5.2.3. Altitude
• Up to 2000m
5.3. Storage Conditions
5.3.1. Temperature
• From -40 to + 70°C
5.3.2. Hygrometry
• Recommendation: to be stored in dry, non-corrosive and non-saline atmospheric conditions.
5.3.3. Storage duration period
• Maximum storage up to a period of 12 months
5.3.4. Storage position
• a maximum of 5 boxes may be stacked vertically
5.3.5. Volume and shipping weights
• Volume LxWxH (mm) inc. packaging: 295x255x115
• Weight: net 1.060 kg/ gross 1.500 kg
6. Standard compliance and marking
Lead free
process
Cmim
CE marking
WEEE
• HZI855 is built in accordance with 2012/19/EU directive:
Standards compliance
Certified according to:
IEC 61010-2-201
IEC 61010-1
GB/T 14048.11 Annex C
Conform to the requirements of: