13.4. Annex IV: Outputs list
These options can be configured in the Parameters / I/O / Inputs menu:
Trigram
Output name
Description
PO1
POS 1 ORDER
Switch position order to go to Source 1
PO2
POS 2 ORDER
Switch position order to go to Source 2
PO0
POS 0 ORDER
Switch position order to go to Source 0
PA0
POS 0 ORDER S1
Switch position order to go to center-off (source 1)
PB0
POS 0 ORDER S2
Switch position order to go to center-off (source 2)
S1A
S1 AVAILABLE
Source 1 available:
Output activated if source 1 is considered as available (see conditions of availability in the dedicated chapter of
the manual).
S2A
S2 AVAILABLE
Source 2 available:
Output activated if source 2 is considered as available (see conditions of availability in the dedicated chapter of
the manual).
SCA
ANY SOURCE AVAIL
Source 1 OR source 2 available:
This output is activated when at least one source (S1 or S2) is available.
S1U
S1 UNAVAIL
Source 1 unavailable:
Output activated if source 1 is not considered as available (see conditions of availability in the dedicated
chapter of the manual) or the source has been inhibited.
S2U
S2 UNAVAIL
Source 2 unavailable:
Output activated if source 2 is not considered as available (see conditions of availability in the dedicated
chapter of the manual) or the source has been inhibited.
AC1
S1 CLOSED
Source 1 closed:
This output has the function of an auxiliary contact. When the controller has the input from the switch to be
in source 1, the output will be active. This also considers the case where with no real information about the
position, the controller works in blind mode.
AC2
S2 CLOSED
Source 2 closed:
This output has the function of an auxiliary contact. When the controller has the input from the switch to be
in source 2, the output will be active. This also considers the case where with no real information about the
position, the controller works in blind mode.
AC0
OFF POSITION
Both sources open (center-off):
This output has the function of an auxiliary contact. When the controller has the input from the switch to be in
center-off, with both switches open, the output will be active. This also considers the case where with no real
information about the position, the controller works in blind mode.
FLT
FAULTS ACTIVE
At least 1 fault is active on the controller. Fault report
ROS
(EXT) TEST ON LOAD
This output is activated if any load test (either HMI or remote order) is ongoing.
ARO
CRIT. ALM. ACTIVE
This alarm output will be active in the case that one of the alarms set in the Alarms menu is active and the
option to use the output to report the alarm is enabled.
-
NONE
OUTPUT NOT USED
GS1
GENSET S1 START
Genset start/stop output. Only available on OUT 5 when the source is a generator (when configured as Genset/
Genset) or on OUT 6 (when configured as Main/Genset with priority on S2).
GS2
GENSET S2 START
Genset start/stop output. Only available on OUT 6 when the source is a generator.
Position orders should not be used with the OUT 5 and
OUT 6 (latching relays).
The latching relays can take up to 2 seconds between
opposite orders (NO to NC or NC to NO) and for added
security when starting a genset will change state based
on the timers or when the backup power is exhausted.