6LE007317A
11
N°
Denomination
Terminal
Description
Characteristics
Recommended Cable
Section
1
Voltage sensing
source 1
L1 / A
Phase 1 / A
1Ph / 3Ph
50 … 332 / 575 VAC
(50/60 Hz)
(+/- 10%)
Impulse V. Withstand Test: 6/8 kV*
Ui 600V
1 … 2.5 mm²
Tightening torque
0.5 … 0.6 Nm
L2 / B
Phase 2 / B
L3 / C
Phase 3 / C
N
Neutral
2
Voltage sensing
source 2
L1 / A
Phase 1 / A
1Ph / 3Ph
50 … 332 / 575 VAC
(50/60 Hz)
(+/- 10%)
Impulse V. Withstand Test: 6/8 kV*
Ui 600V
1 … 2.5 mm²
Tightening torque
0.5 … 0.6 Nm
L2 / B
Phase 2 / B
L3 / C
Phase 3 / C
N
Neutral
3
RS485
+
DATA + (A)
RS485 bus insulated
Modbus cable 25 m =
HTG485H
LiYCY shielded twisted
pair 0.14 to 1.5 mm² /
Tightening torque
0.22 … 0.25 Nm
-
DATA - (B)
NC
Ground
4
Optional Aux. Supply
24 VDC
81
-
12 … 24 VDC
1.5 … 2.5 mm²
Tightening torque
0.5 … 0.6 Nm
82
+
5
Programmable inputs
70
COMMON
Do no connect to any power supply.
To be used with dry contacts
1.5 … 2.5 mm²
Tightening torque
0.5 … 0.6 Nm
71
Input 1
72
Input 2
73
Input 3
74
Input 4
75
Input 5
76
Input 6
6
Programmable
outputs
11-12 NC/
11-14 NO
Output 1
Do no connect to any power supply.
To be used with dry contacts
1.5 … 2.5 mm²
Tightening torque
0.5 … 0.6 Nm
21-22 NC/
21-24 NO
Output 2
31-32 NC/
31-34 NO
Output 3
41-42 NC/
41-44 NO
Output 4
7
Latching relays
51-52 NC/
51-54 NO
Output 5
61-62 NC/
61-64 NO
Output 6
8
Config USB
MicroUSB
USB 2.0
USB port can be used for controller power supply
when not network connected.
MicroUSB Type B
NOTE 1: Use 7mm as stripping length for the controller terminals.
NOTE 2: Use 90°C copper wire for installations with ambient temperature from 35 to 60°C.
When the ambient temperature is above 60°C, Use 105°C copper wire.
NOTE 3: * Impulse voltage withstand tests at 6kV between phases of the same source and 8kV between phases of a different source.