11.1.1. NETWORK parameters menu
The NETWORK menu allows the user with the Configurator profile to configure the installation parameters. Inside NETWORK, there are
5 different submenus:
HZI855
AUTODETECT.:
When selected the function, a pop-up will show asking for a validation from the user to start autodetecting the network
type, the nominal voltage and frequency and the phase rotation. After the autodetection the result can be consulted and modified in the
SETUP menu. Information can be consulted on the SETUP menu.
SETUP:
Settings concerning the installation can be configured here:
HZI855
• Network type: number of poles and wires. See detail on page "NETWORK TYPE" inside this chapter.
• Nominal voltage
• Nominal frequency
• Phase rotation (ABC or ACB // V1 V2 V3 or V1 V3 V2)
• Phase rotation check: it can be enabled or disabled. By default is enabled but it can be disabled for applications where the portable
genset can be replaced frequently by others using different rotation.
• VT used: (used or not used) Voltage Transformers can be used for all applications with V levels above 576V, that it’s the maximum that
the controller can measure directly (ph-ph). Example: 600/480V transformers for 600V applications. Ratio has to be added right after
where it says “VT primary” and “VT secondary”.
In order to save the settings it’ s mandatory to select
SAVE CONFIG on the bottom of the screen or press
OK button for 1.5 s and a pop-up will appear asking for
confirmation before “SAVE AND QUIT ?”.
APPLICATION TYPE:
Settings concerning the usage of the controller (which type of switch, type of sources, priorities…)
HZI855