6LE007317A
29
STATISTICS:
On this screen, user can see all the counters for:
• Cycles (operating hours, number of cycles, cycles in manu, cycles in auto)
• Operations (total and for each position)
• Running hours (total and partial) (partial can be reseted by user)
• Source 1 / Source 2 data (total time in source, partial time, last switch, total time on load)
• Genset 1 / Genset 2 data (total active time, total active time on load, genset start counter)
HZI855
10.8. Genset scheduler / Engine Exerciser Menu
There are 4 selectable engine exerciser programs that are set in order of priority on the display. That means that the program “CUSTOM
1” is priority over the “CUSTOM 2” if both happen to occur at the same time. This is to avoid exercising a genset that it’s being already
exercised. Inside the GENERAL PARAMETERS menu in the same screen, it can also be set a “GENSET IDLE TIMEOUT” time in minutes
to avoid exercising a genset that has just been active just a few minutes/hours before. By default this value is set to 168minutes but if is
not desired, it can be configured to 0 to follow strictly the exerciser programs.
HZI855
For each program (CUSTOM 1-4), the following settings can be defined individually:
Type of test:
type of test that will be performed on this program
• TEST ON LOAD / LOAD TEST: will perform a full test including all the timers and operating the switch (full cycle).
NOTE: on all switches, a TEST ON LOAD will cause a
load supply blackout when testing the transfer function.
• TEST OFF LOAD / NO LOAD TEST: will perform a genset start for the defined time, and a genset stop after the time elapses.
• Nothing / NOT USED
Periodicity:
every how often will the program take place. It can be set yearly, semi-yearly (every 6 months), bimonthly (every 2 months),
monthly, 28 days, biweekly (every 2 weeks), weekly, every 2 days, daily or NON CYCLIC (no repetition, single use).
TEST DURATION:
that’s the time the generator will run with the load before transferring back to priority source (for example, 15minutes).
If using “MANUAL RETRANSFER” specific function, the
transfer to the main source will not take place after this
time, but it will wait user validation to retransfer.