6LE007317A
13
7.3.1.3. Command circuits
By default, the inputs and outputs in the HZI855 are set up as follows:
Type
Terminal N°
Description
By default
Configuration changes when changing
RTSE technology
Breakers
HIB4xxM
Contactors
Inputs
71
IN1: programmable input
Breaker 1 is in position ON
Switch is in position 1
Contactor 1 is in position ON
72
IN2: programmable input
Breaker 2 is in position ON
Switch is in position 2
Contactor 2 is in position ON
73
IN3: programmable input
Breaker 1 is in position OFF
Switch is in position 0
-
74
IN4: programmable input
Breaker 2 is in position OFF
Inhibit
-
75
IN5: programmable input
Breaker 1 is in position TRIP
Manual retransfer
-
76
IN6: programmable input
Emergency stop
RTSE in manual
-
70
Common point for inputs
Outputs
Logic
Impulse
Impulse
Maintained
12/14/11
OUT1: programmable output
Order to close Breaker 1
Order to switch in position 1
Order to close Contactor 1
22/24/21
OUT2: programmable output
Order to close Breaker 2
Order to switch in position 2
Order to close Contactor 2
32/34/31
OUT3: programmable output
Order to open Breaker 1
Order to switch in position 0
-
42/44/41
OUT4: programmable output
Order to open Breaker 2
S1 Available
-
Latching
relays
Logic
Impulse
Impulse
Maintained
52/54/51
OUT 5: genset start relay / programmable output
-
S2 Available
-
62/64/61
OUT 6: genset start relay / programmable output
Order to start Genset
Order to start Genset
-