6LE007317A
33
SWITCH TECHNOLOGY:
Type of switching device / RTSE. Options by default are:
• CIRCUIT BREAKER - (MCCB or ACB) makes reference to standard IEC 60947-2 circuit breakers with 2 positions per device (ON and
OFF), offering the option to have 3 positions when used as a transfer switch (I-0-II).
• HIB4xxM (remote / double supply) makes reference to HIB4xxM Hager switches.
• CONTACTOR - (circuit contactor) makes reference to standard IEC 60947-4-1 contactors with 2 positions per device (ON and OFF),
offering 3 positions (I-0-II). This technology forces the maintained logic for the position order outputs on the controller.
NOTE: To make configuration easier, the controller automatically changes the I/O configuration for position orders and position return
feedback from the switch (using preset values) according to the technology that will be set in the controller.
For safety reasons the change of technology has to be
done on Manual mode and requires the configurator
profile password.
APPLICATION TYPE:
• MAIN - MAIN or UTILITY - UTILITY when using 2 transformers as source 1 and 2.
• MAIN - GEN or UTILITY - GEN when using a transformer and a genset as sources.
SOURCES NAME:
user can enter a name for each source. By default “Source 1” and “Source 2”
SOURCE PRIORITY:
prioritary/preferred source can be set for source 1, source 2 or “no prioritary”. In the “no prioritary” case, the
switch will be closed on either one source or the other as long as they are available.
LOGIC:
according to the inputs of the switch to receive position orders, there are 2 types of logic:
• IMPULSE / PULSE: the output from the controller will send a pulsed signal with a defined duration to the switch to change position.
• CONTACT / MAINTAINED: the output from the controller will close and stay closed indefinitely as long as the switch is requested to
stay in a position. This logic is used mainly with contactors but also with breakers and class PC switches that accept it. In that case,
for example, if position 2 order is activated it will close the output until the transfer, when the output will be off to switch to center-off /
position 0 and after go to position 1.
TEST / EXT TEST ON LOAD PRIO (yes/no):
with this option, when a TEST is taking place, it will stay in test position until it finishes
(timers are elapsed) even if the source is lost.
If the test is set as Unlimited, the switch will stay in test
position until the user finishes the test.
RETRY NUMBER (0-10):
If the position is not reached after a position order, the controller can perform several retries.
RETRY DELAY (0-10000ms):
delay between retries.
PULSE LENGTH (ms):
length of the pulse (only for PULSE mode).
In order to save the settings it’ s mandatory to select
SAVE CONFIG on the bottom of the screen or press
OK button for 1.5 s and a pop-up will appear asking for
confirmation before “SAVE AND QUIT ?”.
OP RANGE S1 and S2:
Permits setting the limits of acceptability for the sources 1 and 2 respectively.
HZI855
HZI855
OV = overvoltage
UV = undervoltage
OF = overfrequency
UF = underfrequency
UB = unbalance