13.3. Annex III: Inputs list
These options can be configured in the Parameters / I/O / Inputs menu:
Trigram
Input name
Description
AC1
SWITCH IN POS 1
Read position 1 from the RTSE
AC2
SWITCH IN POS 2
Read position 2 from the RTSE
AC0
SWITCH IN POS 0
Read position 0 from the RTSE
AC0A
SWITCH A IN POS.0
Read position 0 from the SWITCH on S1
AC0B
SWITCH B IN POS.0
Read position 0 from the SWITCH on S2
MAN
COVER OPEN /
MANUAL MODE
Not in auto, cover open:
This input is connected to the switch to inform the controller that the switch is in maintenance mode (door is
open for servicing). The controller commands will be inhibit but navigation through the menu and dashboards
on the display are allowed. This situation will remain until the input is cleared.
LCK
PADLOCKED
Product padlocked. Message on screen "PADLOCKED", meaning that the RTSE has been padlocked.
Controllers goes to Inhibit mode until input is cleared. The controller commands will be inhibit but navigation
through the menu and dashboards on the display are allowed.
POP
RTSE AVAILABLE
Information coming from the RTSE to inform that the RTSE is operational.
PS1
GO TO POS 1
External order to go to pos 1
Position command only available if the mode is in position CTRL. The last command received has priority.
PS2
GO TO POS 2
External order to go to pos 2
Position command only available if the mode is in position CTRL. The last command received has priority.
PS0
GO TO POS 0
External order to go to pos 0
Position command only available if the mode is in position CTRL. Command 0 has priority over commands I and II.
RT0
RETURN TO 0
Overrides the "Return to 0" function inside SPECIFIC FUNCTIONS
BLK
BLOCKED
Product blocked, meaning that the RTSE is blocked, can't move. The controller will go into Partial Inhibition
(starting the genset if necessary) but not transfering. Message on the display "PRODUCT BLOCKED"
TP1
TRIP BRK 1
Protection on S1 has tripped
TP2
TRIP BRK 2
Protection on S2 has tripped
EST
EMERGENCY SIGN
Emergency off signal. Controller will pilot to go to position 0 (if any). CTRL will be disabled, AUTOMATIC mode
will be off, genset won't be started, "Emergency Off" will be displayed on screen. If Lift/Elevator signal is
enabled, its timers will be respected before giving the command to go to 0.
BCT
BYPASS TIMER
Bypass timer:
Bypasses the current timer on the screen / first one of the list of timers running.
-
NONE
INPUT NOT USED
INH
INHIBIT
Inhibition of the automatism. Mode inhibition (not automatic). CTRL is permitted. Genset won't start if the source
is lost
INHp
PARTIAL INHIBITION
Inhibition of the automatism. Mode inhibition (not automatic). CTRL is permitted. Genset will start if the source is
lost to ensure the supply of the controller, but it will not transfer.
INHt
TOTAL INHIBITION
Inhibition of the automatism. Mode inhibition (not automatic). CTRL is NOT permitted. Genset won't start if the
source is lost
TON
TEST ON LOAD
Start test on load with dedicated test on load timers
TOF
TEST OFF LOAD
Start test off load with dedicated test on load timers
EON
EXT. LOAD
Remote on load test:
If set to UNLIMITED, this order will start the cycle to transfer and the controller will not send an order to go back
to preferred source until the signal is cleared. If set to LIMITED, a pulse on the input will start the test that will
follow the E2T and other timers.
EOF
EXT. NO LOAD
Remote off load test:
If set to UNLIMITED, this order will start the genset and stop the genset according to the external test off load
configuration inside the parameters. If set to LIMITED, a pulse on the input will start the test that will follow the
configured timers.
MRT
MANUAL RETRANS
Manual Retransfer to priority source (touching keypad or via INPUT)
Remote transfer back to the priority source:
This is the same function as "MANUAL RETRANSFER" cleared with the keypad. This variable in the
PARAMETERS/SPECIFIC FUNCTIONS menu must be enabled to validate the operation through this input.