11. Configuration
The configuration on the HZI855 can be done directly on the HMI.
NOTE: The configuration can be done even without cabling the AC or DC supply to the controller, only connecting it to a computer with
an USB cable. The controller will use the USB to power up the screen, buttons and main functions, permitting the configuration through
any of these methods.
11.1. Configuration through the display
How to configure the main parameters manually using the display:
PARAMETERS MENU
Inside the PARAMETERS menu of the Main Menu (accessible by entering the Configurator password, by default 1000) all the main
parameters of the controller can be set:
NETWORK:
Permits the configuration of the nominal voltage and frequency, the phase rotation, the type of switch and the
sources priorities, as well as the operating range where the controller will consider a source as available. See
chapter 11.1.1.
DISPLAY:
Permits selecting the language, setting the date&time and choosing the preferences for the screen and the test
button use (“load test” or “no load test”). See chapter 11.1.2.
TIMERS:
Permits setting all the different operation timers (automatic mode). See chapter 11.1.3.
I/O:
Permits the configuration of the Inputs and Outputs of the controller. See chapter 11.1.4.
COMMUNICATION:
Permits the configuration of the communication parameters such as the Modbus address or the baudrate. See
chapter 11.1.5.
ALARMS:
Permits programming different alarm types that can be linked to outputs and will show the information on the
screen. See chapter 11.1.6.
PASSWORDS:
Permits changing the passwords for the different users. See chapter 11.1.7.
WIZARD:
Permits launch a wizard configuration. See chapter 8.
IMPORTANT NOTE: When doing the configuration
through the display, don’t forget to put the controller
in AUTO mode after the configuration is over to start
the AUTOMATIC mode.