94
DC Inverter Multi
VRF Service Manual
3�4 Clearance Data
NOTE:The picture of the units is only for reference, everything goes by with the real object�
3.4.1 Clearance data of single unit
GMV-Pdm224W/NaB-M, GMV-Pdm280W/NaB-M, GMV-Pdm335W/NaB-M, GMV-Pdm400W/NaB-M, GMV-
Pdm450W/NaB-M, Outline dimensions. (Unit: mm)
>1200
>1000
>1000
>200
>3000
>1000
Electrical
box outlet
on this side
Air outlet
Front
Back
Front
Back
The wall on the four side of the outdoor unit should be in accordance with the above basic space requirement;
In case that the front side and left side (or right side) of the outdoor unit is open space:
No limitation to the height of the wall
For the top wall (e.g. air guard interference), it is required over 3000mm distance between the unit top and the top
wall in principle. In case that the front, back, left and right sides are open to the around space, it is required over 1500mm
distance between the unit top and the top wall. In case the distance is less than 1500mm, or the unit is not open to the
around space, a air inlet is necessary for keeping ventilation
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...