76
DC Inverter Multi
VRF Service Manual
CONTROL
E. Connection of Communication Modules and Centralized Controller
Connection of COM1 of communication module which has 3 COM in total has been introduced as the above. COM2
can connect with another communication module or centralized controller, as shown below:
Step 3: There are two methods of DIP address setting of communication module�
Method 1:
The address of each communication module has been fixed in the factory and marked on the label at the back of it.
It is unnecessary for users to set anything. In addition, the 3-digital DIP can not be dialed to OFF completely, as shown
below:
Label for address of
communication module
Digital switch