112
DC Inverter Multi
VRF Service Manual
The copper pipe shall not be inserted into the branch pipe too deep.
Copper pipe
Branch pipe
Correct connection
Wrong connection
5�7 Welding of Copper Pipe
5.7.1 Braze welding
Materials for braze welding
There are two kinds of braze welding, soft braze welding and hard braze welding. Hard braze welding is required in
this case.
Selection of braze welding
Red red copper:brazing filler metal is Bcu93P(GB 6418),and welding flux is not needed.
Flame flux: capable of preventing the surface of copper pipes from oxidation, recommended for use.
Temperature for braze welding:820-860 (copper pipe becomes light red)
5.7.2 Safety acknowledgement before operation
a. Roll calling of construction personnel and confirmation on their health status.
b. Acknowledgement on work suits(helmets, clothes, safety bags and safety shoes)
c. Description of work location and environment.
d. Job division shall be made. Job content, method and order shall be indicated. Risk prediction activities shall be
performed.
e. “Construction Schedule” shall be worked out.
f. Head of each group shall be assigned
g. Risks of occurrence of an accident such as electric shock or fire shall be indicated.
h. Instructions on how to use electric machinery properly shall be available.
i. Locations marked with “Staff Only” shall be indicated.
j. An application is necessary for use of open flame and shall be reviewed by on-site safety officer for approval.
k. Instructions given by fire authorities shall be accepted in accordance with local laws and regulations.
l. Tools shall be sorted and counted. Upon knocking off for the day, tools shall be sorted and counted. If necessary,
the piping system shall be charged with coolant to avoid exhaustion.
6.7.3 Attention
a. Construction personnel must have relevant operation qualification.
Flame operation must be undertaken by qualified persons in accordance with local laws and regulations.
b. Wear coveralls (cotton for the best), safety shoes, safety helmet, leather gloves, protective goggles and anti-dust
mask.
Welding torch with back fire arrestor shall be used to ensure safety.
c. Take care not to be burned by flame and heating parts.
d. Gas cylinder shall be handled carefully to prevent leakage.
e. Combustible substances in the surrounding areas shall be moved away. If movement is impossible, fire proofing
treatment shall be taken properly, such as being covered by flame-proof enclosure.
f. Good ventilation is necessary to avoid breathe in of harmful gas.
g. Appropriate measures shall be taken if there is a safety problem.
h. Operation on connectors of branch pipes as well as on the surrounding of pipe ends shall be performed on the
ground as possible, because heating is difficult to control at a high place and welded part of a branch pipe is prone to be
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...