100
DC Inverter Multi
VRF Service Manual
4�5 Selection of Refrigerant Piping between Outdoor Unit and Outdoor Unit ( for module unit)
4.5.1 Selection of components between module and module
Notes
Model
Name
Illustration
Sub-assembly
corresponding to
outdoor module
ML01/A
ML01- Liquid pipe
ML01- Air pipe
4.5.2 Selection of pipe diameter between module and module
>30mm
>30mm
Pipe between outdoor unit and indoor unit
Pipe between outdoor unit and
connection sub-assembly
Liquid pipe
Liquid pipe
Gas pipe
Gas pipe
Liquid pipe
Gas pipe
4.5.2.1 Pipe diameter between outdoor unit and connection component
R410a refrigerant system
Single module capacity code C
Gas pipe (mm/inch)
Liquid pipe(mm/inch)
C 280
Φ22.2
Φ9.52
280 C 45
Φ28.6
Φ12.7
4.5.2.2 Pipe diameter between connection component of module and connection component of module
R410a refrigerant system
Sum of capacity code of upstream module C_
Gas pipe (mm/inch)
Liquid pipe(mm/inch)
C 280
Φ22.2
Φ9.52
280 C 450
Φ28.6
Φ12.7
450 C 670
Φ28.6
Φ15.9
670 C 954
Φ34.9
Φ19.05
950 C 1350
Φ41.3
Φ19.05
1350 C 1600
Φ44.5
Φ22.2
1600 C 2100
Φ54.1
Φ25.4
4.5.2.3 Piping used for balancing lubricant
The oil balance pipe is connected by using Φ12.7 copper pipe. For three outdoor units arranged in parallel, one 3-way
joint having an inner diameter of Φ12.9 shall be used in the oil balance pipe.
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...