DC Inverter Multi
VRF Service Manual
4.2.1 For outdoor unit with total rated capacity more than or equal to 60.0kW (See the above picture for the piping
methods)
Allowable (m/ft)
value
Fitting pipe
Total length (actual length) of fitting pipe
500
L1+L2+L3+L4+…+L8+a+b+…+i
Length of the furthest fitting pipe
Actual length
150
L1+L5+L6+L7+L7+ L8+i
Equivalent length
175
Equivalent length of fitting pipe
from the 1st branch joint to farthest indoor unit L(m)
40
L5+L6+L7+L7+ L8+i
Height differences between
indoor unit and outdoor unit
Outdoor unit at upper
50
——
Outdoor unit at lower
40
——
Height differences between indoor units
15
——
4.2.2 For outdoor unit with total rated capacity more than or equal to 20.0kW and less than 60.0kW(See the above picture
for the piping methods)
Allowable (m/ft)
value
Fitting pipe
Total length (actual length) of fitting pipe
300
L1+L2+L3+L4+…+L8+a+b+…+i
Length of the furthest fitting pipe
Actual length
100
L1+L5+L6+L7+L7+ L8+i
Equivalent length
125
Equivalent length of fitting pipe
from the 1st branch joint to farthest indoor unit L(m)
40
L5+L6+L7+L7+ L8+i
Height differences between
indoor unit and outdoor unit
Outdoor unit at upper
50
——
Outdoor unit at lower
40
——
Height differences between indoor units
15
——
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...