DC Inverter Multi
VRF Service Manual
145
Open the Cut-o ff
va lv e of liquid pipes
Open the Cut-o ff valve of
high pr essu re gas pipe s
Open the Cut-o ff valve for
Oil balan ce pipe( when the quan tity
of modula r is mor e than one.)
2) Check if the refrigerant in the system is normal by manomenter connecting liquid pipe and valve of low pressure
gas pipe.
In normal conditions, if the system has been stoodby for more than 3 min, the high pressure and low pressure of the
system will be in balance. The difference between saturation temperature corresponding to pressure value and ambient
temperature (the temp is indoor temp or outdoor temp, whichever is the higher) can’t be more than 5 . Note: make sure
that the system is not started up or it has been energized for more than 10 min since last stop of running (The lower outdoor
ambient temp is, the longer time that the pressure value stabilizes), or the high pressure value of the system will be much
higher than the ambient temp or the low pressure of the sytem will be much lower than the ambient temp)
Eg:
If outdoor ambient temp is 30 , indoor ambient temp is 28 , high pressure value of the system is 28 and low
pressure value is 27 , all differentials between outdoor ambient temp and the others are within 5 which means the
standby pressure of the system is normal.
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...