DC Inverter Multi
VRF Service Manual
105
5�2 Three Principles of Refrigerant Piping Installation
Observe the three principles of refrigerant piping:
Key Factors
Measures to Avoid Failure
Dry
Invasion of outside water
Example: Rainwater, engineering water
Invasion of indoor condensate
Fabrication of
fitting pipe
Vacuuming and
drying
Purge
Clean
Formation of oxides inside
the pipe during welding
Invasion of dust and foreign
articles from outside
Fabrication of
fitting pipe
Purge
Expel with nitrogen 0.05~0.3Mpa
Airtight
Incomplete welding
Leakage from flared port
Leakage from edge
Use suitable materials (copper tube,
soldering bar)
Observe the basic operations for flaring of
fitting pipe
Observe the basic welding procedures
Observe the basic inerfacting procedures
Airtight test
5�3 Installation of Metal Embedded Pipe
Work Order
Metal Embedding Diagram
Installation of metal Embedded Parts
Plotting
Plot the line on ground if possible and use laser to project it onto the roof. This is quick and correct.
Advance Installation of Metal Embedded Parts
Please select according to local codes.
Subsequent Installation of Expansion Bolts
In case that the metal embedded parts cannot be used due to design change, the expansion bolts may be used.
Subsequent Installation of Expansion Bolts
The foot pedal shall be supported on three points if exceeding 2m.
The foot pedal must be fixed securely to the ladder.
Please do not work on the top of ladder.
5�4 Installation of Carriage of Refrigerant pipin
5.4.1 Fixing of horizontal pipe
The refrigerant pipe will extend and shrink with each start or stop of the air conditioner unit (5~10 times / hour).
Under a temperature difference of 80 , this extension may reach 13.84mm for every 10m. To prevent failure, the pipes
must be reinforced as follows.
Spacing between supports
Outer diameter of pipe (mm)
6.35-8.52
Over 12.7
Spacing between supports (m)
Below 1.2
Below 1.5
Note:
If the gas pipe and liquid pipe are suspended together, the size of liquid pipe shall prevail
CAUTION
Never make the pipe directly contact with the fixing metal parts. Thermal insulation shall be provided around the
fixing metal parts; otherwise, condensing will occur.
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...