DC Inverter Multi
VRF Service Manual
15
PRODUCT
Model(Combined unit)
GMV-Pdm1750W4/NaB-M
GMV-Pdm1800W4/NaB-M
Model
GMV-Pdm400W/NaB-M
+GMV-Pdm450W/NaB-M
+GMV-Pdm450W/NaB-M
+GMV-Pdm450W/NaB-M
GMV-Pdm450W/NaB-M
+GMV-Pdm450W/NaB-M
+GMV-Pdm450W/NaB-M
+GMV-Pdm450W/NaB-M
Capacity
Cooling
kW
175.0
180.0
kBtu/h
597.100
614.160
Heating
kW
195.0
200.0
kBtu/h
665.340
682.400
Sound Pressure Level
dB(A)
66
66
Power Supply
V/Hz/Ph
Power input
Cooling
kW
12.45+14.32+14.32+14.32
14.32+14.32+14.32+14.32
Heating
kW
11.2+13.9013.90+13.90
13.9+13.9+13.9+13.9
Current
Cooling
A
22.25+25.6+25.6+25.6
25.6+25.6+25.6+25.6
Heating
A
20.02+24.85+24.85+24.85
24.85+24.85+24.85+24.85
Circuit breaker
A
40+40+40+40
40+40+40+40
Recommended
Power Lines
mm
2
×N
10×5+10×5+10×5+10×5
10×5+10×5+10×5+10×5
Moisture protection
IP24
IP24
Climate Type
T1
T1
Connecting
pipe
Gas
Pipe
mm
Φ54.1
Φ54.1
Inch
17/8
17/8
Liquid
Pipe
mm
Φ25.4
Φ25.4
Inch
1
1
Oil Pipe
mm
Φ12.7
Φ12.7
Inch
1/2
1/2
Connection Method
Brazing Connection
Brazing Connection
Dimensions
of Unit
Width
mm
1340+1340+1340+1340
1340+1340+1340+1340
Depth
mm
770+770+770+770
770+770+770+770
Height
mm
1670+1670+1670+1670
1670+1670+1670+1670
Dimensions
of Package
Width
mm
1420+1420+1420+1420
1420+1420+1420+1420
Depth
mm
850+850+850+850
850+850+850+850
Height
mm
1850+1850+1850+1850
1850+1850+1850+1850
Net Weight
kg
350+370+370+370
370+370+370+370
Gross Weight
kg
380+400+400+400
400+400+400+400
Loading Quantity
( 20’ Container )
unit
——
——
Loading Quantity
( 40’ Container )
unit
——
——
Loading Quantity ( 40’
High Cube Container )
unit
——
——
Notes:
① .
The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
② .
The data will change with the change of products. Refer to those parameters listed on nameplate.
③ .
The charge amount of refrigerant in the list is the datum when there is not drop height vertically between
indoor unit and outdoor unit, without consideration of connection pipe. So calculate the additional charge amount
according to actual condition during installation.
④ .
Section area of lead wire is only applicable for 15-m distance.If above, increase the section area to avoid
overload of current which would cause burnout of lead wire.
⑤ .
The outdoor fan of this unit is without static pressure.If static pressure is required, please specially notice it on
purchase order.
⑥ .
Running condition of cooling: outdoor temperature -5 ~48 ; Running condition of heating: outdoor
temperature -20 ~27 .
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...