18
DC Inverter Multi
VRF Service Manual
PRODUCT
6
Check valve(for STD1/ STD2)
It is used to prevent the high-pressure reverse gas going into the
fixed-frequency compressor at the moment the compressor stops
so as to avoid abnormal startup next time and other problems.
7
Oil separator
It is used to separate the gas and oil so as to
guarantee the reliability of the compressor.
8
Check valve
It is used to prevent the high-pressure reverse gas going
into the modules at the moment that the unit stops
9
Four way valve
It is used to change the status of the heat exchanger.
10
Heat exchanger
It is used to exchanger heat outdoor.
11
Check valve
It is used to reduce the pressure loss of the refrigerant flow.
12
Electronic expansion valve
It is used to adjust the degree of superheat and then
adjust the refrigerant flow to ensure the reliability
and sufficient heat exchange of the system.
13
Receiver
It is used to store unused refrigerant to avoid abnormity.
14
Check valve (for cooling)
It is used under the cooling mode.
15
Solenoid valve (for heating)
It is used under the cooling mode.
16
Check valve
It is used under the cooling mode.
17
Filter-drier
It is used to absorb moisture in the system so as to avoid “ice
plug” or “copper plating” on the surface of the compressor
18
High pressure sensor
It is used to detect the real-time high pressure for
protecting the compressor and other controls.
19
Low pressure sensor
It is used to detect the real-time low pressure for
protecting the compressor and other controls.
20
Solenoid valve (hot gas)
It is used to protect the system running under low pressure
or the compressor starting with pressure difference.
21
Solenoid valve (liquid bypass)
It is used to prevent the compressor running at high temperature.
22
Accumulator
It is used to prevent the compressor running
at high humidity condition.
23
Solenoid valve(INV)
It is used to return the lubricant to the inverter compressor.
24
Solenoid valve(STD1/ STD2)
It is used to return the lubricant to the fixed-frequency compressor.
25
Solenoid valve(Oil balance)
It is used to balance the lubricant among modules.
26
Servicing valve
It is where the low pressure can be measured and
refrigerant can be charged for after-sales maintenance.
27
Liquid pipe
It is the pipe to pass the refrigerant liquid of the system.
28
Gas pipe
It is the pipe to pass the refrigerant gas of the system.
29
Oil balance pipe
It is the pipe to balance the lubricant oil between modules.
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...