DC Inverter Multi
VRF Service Manual
103
Outdoor
unit
Stop elbow
Lquid pipe
Gas pipe
Oil trap
Oil reture trap
6m
6m
6m
6m
6m
Indoor
unit 4
Indoor
unit 1
Indoor
unit 2
Indoor
unit 3
Outdoor unit higher than indoor unit
e. Fabrication dimension of oil trap is as shown below:
A
B(mm)
C(mm)
mm
inch
Φ19.0
3/4
≥34
≤150
Φ22.2
7/8
≥31
≤150
Φ25.4
1/1
≥45
≤150
Φ28.6
9/8
≥45
≤150
Φ34.9
11/8
≥60
≤250
Φ38.1
12/8
≥60
≤350
Φ41.3
13/8
≥80
≤450
Φ44.45
7/4
≥90
≤500
Φ54.1
17/8
≥90
≤500
Содержание CN851W1000
Страница 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Страница 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Страница 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Страница 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Страница 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Страница 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Страница 201: ...196 DC Inverter Multi VRF Service Manual GMV Pdm335W NaB M GMV Pdm400W NaB M GMV Pdm450W NaB M ...
Страница 233: ...JF00300207 ...