DC Inverter Multi
VRF Service Manual
111
Enlarged view A
Enlarged view B
Connection of branch pipe
The Y-type branch pipe is installed with additional tube. The purpose is to adjust the different pipe diameters. If the
pipe size selected on site is different from the size of branch connector, please use the pipe cutter to cut from the middle of
different connection pipes and remove the burrs. Then, insert the copper pipe to appropriate depth. The branch pipes from
Gree are all provided with positioning mark.
Branch pipe
Copper pipe
Cut from the middle
of copper pipe as needed
Do not use the connection method that the copper pipe is cased on branch pipe of smaller diameter.
Copper pipe
Branch pipe
Correct connection
Wrong connection