B-68
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F141
ENUMERATION: SELF TEST ERRORS
F142
ENUMERATION: EVENT RECORDER ACCESS FILE TYPE
0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause
F143
UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)
A bit value of 0 = no error, 1 = error
F144
ENUMERATION: FORCED CONTACT INPUT STATE
0 = Disabled, 1 = Open, 2 = Closed
F145
ENUMERATION: ALPHABET LETTER
F146
ENUMERATION: MISCELLANEOUS EVENT CAUSES
bitmask
error
0
Any Self Tests
1
Maintenance Alert
10
FlexLogic Error Token
11
Equipment Mismatch
13
Unit Not Programmed
14
System Exception
15
Maintenance Alert
16
Ethernet Switch Failure
17
Maintenance Alert
18
Maintenance Alert
19
Maintenance Alert
20
Maintenance Alert
21
Maintenance Alert
27
Remote Device Off
28
Direct Device Off
29
Maintenance Alert
30
Any Minor Error
31
Any Major Error
32
DSP Error
33
No DSP Interrupts
34
Unit Not Calibrated
35
EEPROM Data Error
36
SRAM Data Error
37
Program Memory
38
Watchdog Error
39
Low On Memory
40
Prototype Firmware
41
Module Failure 01
42
Module Failure 02
43
Module Failure 03
44
Module Failure 04
45
Module Failure 05
46
Module Failure 06
47
Module Failure 07
48
Module Failure 08
49
Module Failure 09
50
Incompatible H/W
51
Maintenance Alert
52
Maintenance Alert
53
Maintenance Alert
54
Maintenance Alert
55
Maintenance Alert
56
Maintenance Alert
bitmask
type
bitmask
type
bitmask
type
bitmask
type
0
null
7
G
14
N
21
U
1
A
8
H
15
O
22
V
2
B
9
I
16
P
23
W
3
C
10
J
17
Q
24
X
4
D
11
K
18
R
25
Y
5
E
12
L
19
S
26
Z
6
F
13
M
20
T
bitmask
definition
0
Events Cleared
1
Oscillography Triggered
2
Date/time Changed
3
Default Settings Loaded
4
Test Mode On
5
Test Mode Off
6
Power On
7
Power Off
8
Relay In Service
9
Relay Out Of Service
10
Watchdog Reset
11
Oscillography Clear
12
Reboot Command
13
Led Test Initiated
14
Flash Programming
15
Fault Report Trigger
16
User Programmable Fault Report Trigger
17
Corrupt DSP Program
18
Reload DSP Settings
19
DSP Hardware Error
20
Ethernet Port 1 Offline
21
Ethernet Port 2 Offline
22
Ethernet Port 3 Offline
23
Ethernet Port 4 Offline
24
Ethernet Port 5 Offline
25
Ethernet Port 6 Offline
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...