GE Multilin
N60 Network Stability and Synchrophasor Measurement System
6-5
6 ACTUAL VALUES
6.2 STATUS
6
6.2.6 VIRTUAL OUTPUTS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
VIRTUAL OUTPUTS
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output.
6.2.7 REMOTE DEVICES
a) STATUS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
REMOTE DEVICES STATUS
The present state of up to 16 programmed remote devices is shown here. The
ALL REMOTE DEVICES ONLINE
message indi-
cates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one
required remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
REMOTE DEVICES STATISTICS
Ö
REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The
StNum
number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The
SqNum
number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
VIRTUAL OUTPUTS
Virt Op 1
Off
Range: On, Off
MESSAGE
Virt Op 2
Off
Range: On, Off
↓
MESSAGE
Virt Op 96
Off
Range: On, Off
REMOTE DEVICES
STATUS
All REMOTE DEVICES
ONLINE: No
Range: Yes, No
MESSAGE
REMOTE DEVICE 1
STATUS: Offline
Range: Online, Offline
MESSAGE
REMOTE DEVICE 2
STATUS: Offline
Range: Online, Offline
↓
MESSAGE
REMOTE DEVICE 16
STATUS: Offline
Range: Online, Offline
REMOTE DEVICE 1
REMOTE DEVICE 1
StNum: 0
MESSAGE
REMOTE DEVICE 1
SqNum: 0
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...