GE Multilin
N60 Network Stability and Synchrophasor Measurement System
3-37
3 HARDWARE
3.4 MANAGED ETHERNET SWITCH MODULES
3
2.
Enter “3.94.247.229” in the
IP Address
field and “255.255.252.0” in the
Subnet Mask
field, then click
OK
.
The software will send the new settings to the N60 and prompt as follows when complete.
3.
Cycle power to the N60 and switch module to activate the new settings.
b) SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE
The N60 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file con-
tains the advanced configuration details for the switch not contained within the standard N60 settings file.
This feature allows the switch module settings to be saved locally before performing firmware upgrades. Saving settings
files is also highly recommended before making any change to the module configuration or creating new setting files.
The following procedure describes how to save local settings files for the Ethernet switch module.
1.
Select the desired device from site tree in the online window.
2.
Select the
Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File >
Retreive Settings File
item from the device settings tree.
The system will request the name and destination path for the settings file.
3.
Enter an appropriate folder and file name and click
Save
.
All settings files will be saved as text files and the corresponding file extension automatically assigned.
c) UPLOADING ETHERNET SWITCH SETTINGS FILES TO THE MODULE
The following procedure describes how to upload local settings files to the Ethernet switch module. It is highly recom-
mended that the current settings are saved to a settings file before uploading a new settings file.
1.
Select the desired device from site tree in the online window.
2.
Select the
Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File >
Transfer Settings File
item from the device settings tree.
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...