GE Multilin
N60 Network Stability and Synchrophasor Measurement System
5-73
5 SETTINGS
5.3 SYSTEM SETUP
5
5.3.6 PHASOR MEASUREMENT UNIT
a) MAIN MENU
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
PHASOR MEASUREMENT UNIT
The N60 Network Stability and Synchrophasor Measurement System is provided with an optional phasor
measurement unit feature. This feature is specified as a software option at the time of ordering. The num-
ber of phasor measurement units available is also dependent on this option. Refer to the
Ordering
section
of chapter 2 for additional details.
The
PHASOR MEASUREMENT UNIT
menu allows specifying basic parameters of the measurements process such as signal
source, ID and station name, calibration data, triggering, recording, and content for transmission on each of the supported
ports. The reporting ports menus allow specifying the content and rate of reporting on each of the supported ports.
Precise IRIG-B input is vital for correct synchrophasor measurement and reporting. A DC level shift IRIG-B receiver
must
be used for the phasor measurement unit to output proper synchrophasor values.
The PMU settings are organized in five logical groups as follows.
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
PHASOR MEASUREMENT UNIT
ÖØ
PHASOR MEASUREMENT UNIT 1(4)
PHASOR MEASUREMENT
UNIT
PHASOR MEASUREMENT
UNIT 1
See below.
MESSAGE
PHASOR MEASUREMENT
UNIT 2
See below.
MESSAGE
PHASOR MEASUREMENT
UNIT 3
See below.
MESSAGE
PHASOR MEASUREMENT
UNIT 4
See below.
MESSAGE
REPORTING OVER
NETWORK
PHASOR MEASUREMENT
UNIT 1
PMU 1 BASIC
CONFIGURATION
MESSAGE
PMU 1
CALIBRATION
MESSAGE
PMU 1
COMMUNICATION
MESSAGE
PMU 1
TRIGGERING
MESSAGE
PMU 1
RECORDING
NOTE
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...