GE Multilin
N60 Network Stability and Synchrophasor Measurement System
5-27
5 SETTINGS
5.2 PRODUCT SETUP
5
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
GGIO1 STATUS CONFIGURATION
The
NUMBER OF STATUS POINTS IN GGIO1
setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the
NUMBER OF STATUS POINTS IN GGIO1
setting will not take effect until
the N60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
GGIO2 CONTROL...
Ö
GGIO2 CF SPSCO 1(64)
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the N60
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
GGIO4 ANALOG CONFIGURATION
The
NUMBER OF ANALOG POINTS
setting determines how many analog data points will exist in GGIO4. When this value is
changed, the N60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
The
SCAN PERIOD OF ANALOG POINTS
setting specifies the IEC 61850 report scan period in milliseconds.
When the transmit rate of the analog GOOSE communications is configured at a rate less than 1000 ms, only one
PMU can be used in the N60.
GGIO1 STATUS
CONFIGURATION
NUMBER OF STATUS
POINTS IN GGIO1: 8
Range: 8 to 128 in steps of 8
MESSAGE
GGIO1 INDICATION
1
Off
Range: FlexLogic™ operand
MESSAGE
GGIO1 INDICATION
2
Off
Range: FlexLogic™ operand
↓
MESSAGE
GGIO1 INDICATION 128
Off
Range: FlexLogic™ operand
GGIO2 CF SPCSO 1
GGIO2 CF SPCSO 1
CTLMODEL: 1
Range: 0, 1, or 2
GGIO4 ANALOG
CONFIGURATION
NUMBER OF ANALOG
POINTS IN GGIO4:
8
Range: 4 to 32 in steps of 4
MESSAGE
SCAN PERIOD OF
ANALOG POINTS: 1000 ms
Range: 250 to 5000 ms in steps of 10
MESSAGE
GGIO4 ANALOG 1
MEASURED VALUE
MESSAGE
GGIO4 ANALOG 2
MEASURED VALUE
↓
MESSAGE
GGIO4 ANALOG 32
MEASURED VALUE
NOTE
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...