5-70
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
5.3 SYSTEM SETUP
5 SETTINGS
5
5.3.5 DISCONNECT SWITCHES
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
SWITCHES
Ö
SWITCH 1
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to cre-
ate an interlocking functionality. For greater security in determination of the switch pole position, both the 52/a and 52/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the N60.
•
SWITCH 1 FUNCTION:
This setting enables and disables the operation of the disconnect switch element.
•
SWITCH 1 NAME:
Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used
in flash messages related to disconnect switch 1.
•
SWITCH 1 MODE:
This setting selects “3-pole” mode, where all disconnect switch poles are operated simultaneously,
or “1-pole” mode where all disconnect switch poles are operated either independently or simultaneously.
SWITCH 1
SWITCH 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
SWITCH 1 NAME:
SW 1
Range: up to 6 alphanumeric characters
MESSAGE
SWITCH 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
SWITCH 1 OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 BLK OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 BLK CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
SWTCH 1
Φ
A/3P CLSD:
Off
Range: FlexLogic™ operand
MESSAGE
SWTCH 1
Φ
A/3P OPND:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
B CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
B OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
C CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
C OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 Toperate:
0.070 s
Range: 0.000 to 2.000 s in steps of 0.001
MESSAGE
SWITCH 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
SWITCH 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...