GE Multilin
N60 Network Stability and Synchrophasor Measurement System
5-31
5 SETTINGS
5.2 PRODUCT SETUP
5
If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the N60 clock for
as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained from the SNTP server is used. If
either SNTP or IRIG-B is enabled, the N60 clock value cannot be changed using the front panel keypad.
To use SNTP in unicast mode,
SNTP SERVER IP ADDR
must be set to the SNTP/NTP server IP address. Once this address is
set and
SNTP FUNCTION
is “Enabled”, the N60 attempts to obtain time values from the SNTP/NTP server. Since many time
values are obtained and averaged, it generally takes three to four minutes until the N60 clock is closely synchronized with
the SNTP/NTP server. It may take up to two minutes for the N60 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the
SNTP SERVER IP ADDR
setting to “0.0.0.0” and
SNTP FUNCTION
to “Enabled”. The
N60 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The N60 waits up to eighteen
minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The UR-series relays do not support the multicast or anycast SNTP functionality.
l) ETHERNET SWITCH
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
ETHERNET SWITCH
These settings appear only if the N60 is ordered with an Ethernet switch module (type 2S or 2T).
The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings
are used in advanced network configurations. Please consult the network administrator before making changes to these
settings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings.
The
PORT 1 EVENTS
through
PORT 6 EVENTS
settings allow Ethernet switch module events to be logged in the event
recorder.
5.2.5 MODBUS USER MAP
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
MODBUS USER MAP
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
ADDRESS
line (this value must be converted from hex to decimal format). The corresponding value is dis-
played in the
VALUE
line. A value of “0” in subsequent register
ADDRESS
lines automatically returns values for the previous
ADDRESS
lines incremented by “1”. An address value of “0” in the initial register means “none” and values of “0” will be dis-
played for all registers. Different
ADDRESS
values can be entered as required in any of the register positions.
ETHERNET SWITCH
SWITCH IP ADDRESS:
127.0.0.1
Range: standard IP address format
MESSAGE
SWITCH MODBUS TCP
PORT NUMBER: 502
Range: 1 to 65535 in steps of 1
MESSAGE
PORT 1 EVENTS:
Disabled
Range: Enabled, Disabled
MESSAGE
PORT 2 EVENTS:
Disabled
Range: Enabled, Disabled
↓
MESSAGE
PORT 6 EVENTS:
Disabled
Range: Enabled, Disabled
MODBUS USER MAP
ADDRESS
1:
0
VALUE:
0
Range: 0 to 65535 in steps of 1
MESSAGE
ADDRESS
2:
0
VALUE:
0
Range: 0 to 65535 in steps of 1
↓
MESSAGE
ADDRESS 256:
0
VALUE:
0
Range: 0 to 65535 in steps of 1
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...