B-70
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F167
ENUMERATION: SIGNAL SOURCE
0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4,
4 = SRC 5, 5 = SRC 6
F168
ENUMERATION: INRUSH INHIBIT FUNCTION
0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd
F170
ENUMERATION: LOW/HIGH OFFSET and GAIN
TRANSDUCER INPUT/OUTPUT SELECTION
0 = LOW, 1 = HIGH
F171
ENUMERATION: TRANSDUCER CHANNEL INPUT TYPE
0 = dcmA IN, 1 = Ohms IN, 2 = RTD IN, 3 = dcmA OUT
F172
ENUMERATION: SLOT LETTERS
F173
ENUMERATION: DCMA INPUT/OUTPUT RANGE
F174
ENUMERATION: TRANSDUCER RTD INPUT TYPE
0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel,
2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
F175
ENUMERATION: PHASE LETTERS
0 = A, 1 = B, 2 = C
F176
ENUMERATION: SYNCHROCHECK DEAD SOURCE SELECT
F177
ENUMERATION: COMMUNICATION PORT
0 = None, 1 = COM1-RS485, 2 = COM2-RS485,
3 = Front Panel-RS232, 4 = Network - TCP, 5 = Network - UDP
F178
ENUMERATION: DATA LOGGER RATES
0 = 1 sec, 1 = 1 min, 2 = 5 min, 3 = 10 min, 4 = 15 min,
5 = 20 min, 6 = 30 min, 7 = 60 min, 8 = 15 ms, 9 = 30 ms,
10 = 100 ms, 11 = 500 ms
F180
ENUMERATION: PHASE/GROUND
0 = PHASE, 1 = GROUND
F181
ENUMERATION: ODD/EVEN/NONE
0 = ODD, 1 = EVEN, 2 = NONE
F183
ENUMERATION: AC INPUT WAVEFORMS
F184
ENUMERATION: REMOTE DEVICE GOOSE DATASET
bitmask
slot
bitmask
slot
bitmask
slot
bitmask
slot
0
F
4
K
8
P
12
U
1
G
5
L
9
R
13
V
2
H
6
M
10
S
14
W
3
J
7
N
11
T
15
X
bitmask
dcmA input/output range
0
0 to –1 mA
1
0 to 1 mA
2
–1 to 1 mA
3
0 to 5 mA
4
0 to 10 mA
5
0 to 20 mA
6
4 to 20 mA
bitmask
synchrocheck dead source
0
None
1
LV1 and DV2
2
DV1 and LV2
3
DV1 or DV2
4
DV1 Xor DV2
5
DV1 and DV2
bitmask
definition
0
Off
1
8 samples/cycle
2
16 samples/cycle
3
32 samples/cycle
4
64 samples/cycle
value
GOOSE dataset
0
Off
1
GooseIn 1
2
GooseIn 2
3
GooseIn 3
4
GooseIn 4
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...