E-10
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
E.2 DNP POINT LISTS
APPENDIX E
E
E.2.3 COUNTERS
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is per-
formed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.
A counter freeze command has no meaning for counters 8 and 9. N60 Digital Counter values are represented as 32-bit
integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative
counter values.
BINARY COUNTERS
Static (Steady-State) Object Number:
20
Change Event Object Number:
22
Request Function Codes supported:
1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear),
10 (freeze and clear, noack), 22 (assign class)
Static Variation reported when variation 0 requested:
1 (32-Bit Binary Counter with Flag)
Change Event Variation reported when variation 0 requested:
1 (32-Bit Counter Change Event without time)
Change Event Buffer Size:
10
Default Class for all points:
3
FROZEN COUNTERS
Static (Steady-State) Object Number:
21
Change Event Object Number:
23
Request Function Codes supported:
1 (read)
Static Variation reported when variation 0 requested:
1 (32-Bit Frozen Counter with Flag)
Change Event Variation reported when variation 0 requested:
1 (32-Bit Frozen Counter Event without time)
Change Event Buffer Size:
10
Default Class for all points:
3
Table E–4: BINARY AND FROZEN COUNTERS
POINT
INDEX
NAME/DESCRIPTION
0
Digital Counter 1
1
Digital Counter 2
2
Digital Counter 3
3
Digital Counter 4
4
Digital Counter 5
5
Digital Counter 6
6
Digital Counter 7
7
Digital Counter 8
8
Oscillography Trigger Count
9
Events Since Last Clear
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...