2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
2.2SPECIFICATIONS
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
2.2.1 PROTECTION ELEMENTS
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE IOC
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0
×
CT rating:
±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0
×
CT rating
±1.5% of reading
Overreach:
<2%
Pickup delay:
0.00 to 600.00 s in steps of 0.01
Reset delay:
0.00 to 600.00 s in steps of 0.01
Operate time:
<16 ms at 3
×
pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3
×
pickup at 60 Hz
(Neutral IOC)
Timing accuracy:
Operate at 1.5
×
pickup
±3% or ±4 ms (whichever is greater)
SENSITIVE DIRECTIONAL POWER
Measured power:
3-phase, true RMS
Number of stages:
2
Characteristic angle:
0 to 359° in steps of 1
Calibration angle:
0.00 to 0.95° in steps of 0.05
Minimum power:
–1.200 to 1.200 pu in steps of 0.001
Pickup level accuracy:
±1% or ±0.001 pu, whichever is greater
Hysteresis:
2% or 0.001 pu, whichever is greater
Pickup delay:
0 to 600.00 s in steps of 0.01
Time accuracy:
±3% or ±4 ms, whichever is greater
Operate time:
50 ms
PHASE UNDERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Curve shapes:
GE IAV Inverse;
Definite Time (0.1s base curve)
Curve multiplier:
Time dial = 0.00 to 600.00 in steps of
0.01
Timing accuracy:
Operate at < 0.90
×
pickup
±3.5% of operate time or ±4 ms (which-
ever is greater)
PHASE OVERVOLTAGE
Voltage:
Phasor only
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 in steps of 0.01 s
Operate time:
<
30 ms at 1.10
×
pickup at 60 Hz
Timing accuracy:
±3% or ±4 ms (whichever is greater)
UNDERFREQUENCY
Minimum signal:
0.10 to 1.25 pu in steps of 0.01
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% or 4 ms, whichever is greater
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
OVERFREQUENCY
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup – 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% or 4 ms, whichever is greater
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
RATE OF CHANGE OF FREQUENCY
df/dt trend:
increasing, decreasing, bi-directional
df/dt pickup level:
0.10 to 15.00 Hz/s in steps of 0.01
df/dt dropout level:
96% of pickup
df/dt level accuracy:
80 mHz/s or 3.5%, whichever is greater
Overvoltage supv.:
0.100 to 3.000 pu in steps of 0.001
Overcurrent supv.:
0.000 to 30.000 pu in steps of 0.001
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Time accuracy:
±3% or ±4 ms, whichever is greater
95% settling time for df/dt: < 24 cycles
Operate time:
12 cycles at 2
×
pickup
8 cycles at 3
×
pickup
5 cycles at 5
×
pickup
SYNCHROCHECK
Max voltage difference:
0 to 400000 V in steps of 1
Max angle difference:
0 to 100
°
in steps of 1
Max freq. difference:
0.00 to 2.00 Hz in steps of 0.01
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
NOTE
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...