GE Multilin
N60 Network Stability and Synchrophasor Measurement System
5-85
5 SETTINGS
5.3 SYSTEM SETUP
5
k) PMU RECORDING
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
PHASOR...
ÖØ
PHASOR MEASUREMENT UNIT 1
ÖØ
PMU 1 RECORDING
Each logical phasor measurement unit (PMU) is associated with a recorder. The triggering condition is programmed via the
PMU 1 TRIGGERING
menu. The recorder works with polar values using resolution as in the PMU actual values.
PMU 1
RECORDING
PMU 1 RECORDING
RATE: 10/sec
Range: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times per
second
MESSAGE
PMU 1 NO OF TIMED
RECORDS: 10
Range: 2 to 128 in steps of 1
MESSAGE
PMU 1 TRIGGER MODE:
Automatic Overwrite
Range: Automatic Overwrite, Protected
MESSAGE
PMU 1 TIMED TRIGGER
POSITION: 10%
Range: 1 to 50% in steps of 1
MESSAGE
PMU 1 REC PHS-1:
PMU 1 V1
Range: available synchrophasor values
MESSAGE
PMU 1 REC PHS-1
NM: GE-UR-PMU-V1
Range: 16 character ASCII string
↓
MESSAGE
PMU 1 REC PHS-14:
Off
Range: available synchrophasor values
MESSAGE
PMU 1 REC PHS-14
NM: GE-UR-PMU-PHS-14
Range: 16 character ASCII string
MESSAGE
PMU 1 REC A-CH-1:
Off
Range: available FlexAnalog values
MESSAGE
PMU 1 REC A-CH-1
NM: AnalogChannel1
Range: 16 character ASCII string
↓
MESSAGE
PMU 1 REC A-CH-8:
Off
Range: available FlexAnalog values
MESSAGE
PMU 1 REC A-CH-8
NM: AnalogChannel8
Range: 16 character ASCII string
MESSAGE
PMU 1 REC D-CH-1:
Off
Range: FlexLogic™ operand
MESSAGE
PMU 1 REC D-CH-1
NM: DigitalChannel1
Range: 16 character ASCII string
↓
MESSAGE
PMU 1 REC D-CH-16:
Off
Range: FlexLogic™ operand
MESSAGE
PMU 1 REC D-CH-16
NM: DigitalChannel16
Range: 16 character ASCII string
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...