CHAPTER 6: METERING
ARC FLASH
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
6–19
Arc Flash
Path
:
Metering > Arc Flash > Arc Flash 1
HS Phase Current A/B/C
Range: 0.00 to 120000.00 A in steps of 0.01
HS Ground Current
Range: 0.00 to 120000.00 A in steps of 0.01
RTDs
Path
:
Metering > RTDs
NOTE
NOTE:
The Temperature can be displayed in Celsius or Fahrenheit degrees. The selection is made
in
Setpoints > Device > Installation > Temperature Display
.
Hottest Stator RTD #
Range: 1 to 13
Hottest Stator RTD Temp
Range: -40 to 250°C
This value shows the hottest RTD temperature from the group of RTDs when setpoint
Application is programmed as Stator. The other conditions to display this value are: RTD
n must not be Disabled (both Trip and Alarm functions) and must not be detected
Shorted or Open RTD.
Hottest Bearing RTD #
Range: 1 to 13
Hottest Bearing RTD Temp
Range: -40 to 250°C
This value shows the hottest RTD temperature from the group of RTDs when setpoint
Application is programmed as Bearing.
RTD 1(13)
Range: -40 to 250°C (temperatures < -40°C are displayed as “Shorted” and temperatures >
250°C are displayed as “Open RTD”)
Содержание Multilin 889
Страница 10: ...VIII 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Страница 126: ...3 48 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE INTERFACE CHAPTER 3 INTERFACES ...
Страница 530: ...4 400 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Страница 575: ...CHAPTER 8 MAINTENANCE ENVIRONMENTAL HEALTH REPORT 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL 8 3 ...
Страница 580: ...A 4 889 GENERATOR PROTECTION SYSTEM INSTRUCTION MANUAL REVISION HISTORY CHAPTER A APPENDIX A ...