CHAPTER 4: SETPOINTS
PROTECTION
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–201
REVERSE PICKUP
Range: 0.005 to 3.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
This setting defines the Pickup level for the overcurrent unit of the element in the reverse
direction.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset