4–68
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM
CHAPTER 4: SETPOINTS
System
Figure 4-15: System Display Hierarchy
Current Sensing
Path:
Setpoints > System > Current Sensing > CT Bank 1-J1
CT BANK NAME
Range: Any combination of 13 alphanumeric characters
Default: CT Bank 1-J1
PHASE CT PRIMARY
Range: 1 A to 12000 A in steps of 1A
Default: 500 A
Enter the phase CT primary current for current sensing bank J1.
GROUND CT PRIMARY
Range: 1 A to 12000 A
Default: 500 A
Enter the rated Ground CT primary current for the ground current input for the selected
Current 1 bank.
Path:
Setpoints > System > Current Sensing > Current Bank 2-K1
CT BANK NAME
Range: Any combination of 13 alphanumeric characters
Default: CT Bank 2-K1